COOLING UNIT PS1245CO is designed for flashlamp-pumped lasers and
provides effective heat removal and high stability of laser rod
temperature. This enables long term operation of your laser at maximum
efficiency. Unit is assembled in 19“ chase and may be used completing
the powering group of laser systems. Also it can be mounted into the 19
rack.
Operation of cooling unit is based on water-to-air
heat exchange. Deionised or distilled water of 1-20 µS/cm
conductivity is used in laser loop of cooling unit.
Temperature stability of coolant is maintained by electronic circuit.
Stabilization temperature is set by 10-turn potentiometer within
25-45°C (another range is available according to customers
requests).
Indication of coolant and set temperature,
coolant level, overheat and pressure absence in laser loop is provided
on front panel of cooling unit.
Blocking and protection
circuitry in case of overheating, pressure absence or coolant level is
out of low limits sends interrupt signal to interlock connector to which
protection circuitry of laser powering might be connected. Coolant pump
will be stopped in case of pressure absence or coolant level is out of
limits.
Deionisation and filtration of coolant eliminates a
build up on the flashlamp, reduces servicing need and allows laser
operation at maximum efficiency in day-to-day use.
指标参数
技术参数:
Water-to-air cooling unit Cooling capacity up to 2 kW (0.5, 1, 1.5, 2 kW options available) Laser loop coolant flow up to 7 l/min Pressure up to 3.5 bar Coolant temperature indication Water filtration and deionisation 19 x 7U case 25-45°C temperature range